A Simple Action is an action which sets an output at ON/OFF state, with a specific timer and dimmer value.

204 (0-203) Simple Actions can be programmed. When you want to activate simple action 105 for example, you can use Basic Action BA 0 105.

Definition of the 5 bytes used:

  1. Config: bit10=00 -> put selected output to off, bit10=01 -> put selected output to on, bit10=10 -> toggle selected output, bit10=11 -> set or clear validation bit, bit3=0 -> use standard timer value from output pages, bit3=1 -> use timer value from simple action byte 3 and 4, bit54=00 -> clear validation bit, bit54=01 -> set validation bit, bit54=10 -> toggle validation bit
  2. Selected output (0-239), 240 – 255 will be ignored and the function will be aborted with the only exception of 241 (all off) when config/Bit10=00. When config/bit10=11, validation number (0-255) will be found in this byte.
  3. Timer byte 0, LSB for timer value
  4. Timer byte 1, MSB for timer value
  5. Dimmer value (0-63), when switched on, this dimmer value will be used