Difference between revisions of "Master Release Notes"

From OpenMotics
Jump to navigation Jump to search
Line 10: Line 10:
 
=== Added functionality ===
 
=== Added functionality ===
 
* Switch type selection: For installations that needs toggle switches instead of push buttons, the needed changes are added in the firmware to support this functionality. In the eeprom, an additional page (page 97) is used to configure the switch type of each input. For more details, please see [[Memory Model]].
 
* Switch type selection: For installations that needs toggle switches instead of push buttons, the needed changes are added in the firmware to support this functionality. In the eeprom, an additional page (page 97) is used to configure the switch type of each input. For more details, please see [[Memory Model]].
To change this setting, you can use the Openmotics portal or this can be done manual by using maintenance mode:
+
To change this setting, you can use the Openmotics portal or this can be done manual by using maintenance mode.
 +
 
 +
example:
 
<code>eeprom write 97 62 0</code>
 
<code>eeprom write 97 62 0</code>
 
will program switch 62 as toggle switch
 
will program switch 62 as toggle switch

Revision as of 20:01, 28 September 2014

General

The Master firmware is published Open Source since firmware release V3.140.104. Below you'll find all the changes since that release.

V3.140.107

Date: 28/9/2014

Resolved bugs

  • None

Added functionality

  • Switch type selection: For installations that needs toggle switches instead of push buttons, the needed changes are added in the firmware to support this functionality. In the eeprom, an additional page (page 97) is used to configure the switch type of each input. For more details, please see Memory Model.

To change this setting, you can use the Openmotics portal or this can be done manual by using maintenance mode.

example: eeprom write 97 62 0 will program switch 62 as toggle switch eeprom activate will activate the changes made in eeprom

V3.140.105

Date: 21/8/2014

Resolved bugs

  • Time bug: In some very rare occasions, the real time clock reports an hour higher than 23 making the time synchronization fail between the master and gateway controller. An additional check in the Master as well as the gateway controller has been added to avoid this sync failure.

Added functionality

  • None