Led function

From OpenMotics
Revision as of 08:12, 7 June 2016 by Wilbert (talk | contribs) (Created page with "== Led Function == {| class="wikitable" width="60%" ! width="5%"|Led function !Description |- !<div align="center">0</div> |If the linked output if Off, switch off led, if the...")
(diff) ← Older revision | Latest revision (diff) | Newer revision → (diff)
Jump to navigation Jump to search

Led Function

Led function Description
0
If the linked output if Off, switch off led, if the linked output is on, Switch Led ON at brightness Level 1
1
If the linked output if Off, switch off led, if the linked output is on, Switch Led ON at brightness Level 2
...
...
15
If the linked output if Off, switch off led, if the linked output is on, Switch Led ON at brightness Level 16 (Max brightness)
16
If the linked output if Off, switch off led, if the linked output is on, Fast blinking Led at brightness Level 1
17
If the linked output if Off, switch off led, if the linked output is on, Fast blinking Led at brightness Level 2
...
...
8
RS485 error: Output Device is not responding. ID of the device can be found in ID0..ID3
9
RS485 error: Output Device is responding but not with “OK” message or wrong module is answering
10
RS485 error: Network errors, check termination resistors. ID of the device can be found in ID0..ID3
11
# of inputs found in the EEPROM of the Master (EEPROM page 0 line 1) are higher than 30 and is not valid. ID0..ID3 = null. Number of input modules is zero now
12
# of outputs found in the EEPROM of the Master (EEPROM page 0 line 1) are higher than 30 and is not valid. ID0..ID3 = null. Number of output modules is zero now
13
Too many intelligent actions are created, most likely due to a loop. A loop can be caused by using group actions that call themselves
14
Unexpected character received (i.e.: a letter where a value was expected)
15
Output to switch off is not in a valid range (<239)
16
Output to switch on is not in a valid range (<239)
17
Wrong or unrecognized instruction
18
Wrong value used in reading the EEPROM
19
A value with more than 5 digits is not accepted
20
Wrong value used in reading the EEPROM
21
Wrong value used in reading output timer values
22
Wrong value used in writing output timer values
23
Values out of range or wrong number of arguments
24
Overflow scheduled action queue
25
Auto Initialization byte (Page0/Byte14): System is in auto initialization mode, instruction add in CLI mode can’t be used
26
Duplicate ID found on the network during initialization mode, bus will be reinitialized to solve the problem. User must press the initialization/discovery button on the Module again to initialize the appropriate Module
27
Wrong CRC received from remote module or CRC information is missing
28
RS485 error: Output Device configured as Roller/Shutter in Large Installation mode is responding but not with “OK” message or wrong module is answering