The AIO has an onboard FRAM connected via I2C to the DSPIC33E (The Master). FRAM is used to keep track of the real-time change, Eeprom is used to store the settings. This document describes the FRAM memory locations used.

General Configuration Bytes

Page 0 -> General data

Data output modules

Page 1 – 10 -> Contains data of the output modules, 32 bytes per module, 8 modules per page, 10 pages (80 modules maximum, 640 outputs -> 0-639)
Page Byte
1 x
This page is entirely used for output module 0-7:
* Module 0: Byte0..31
* Module 1: Byte32..63
* ...
Page Byte
2 x
This page is entirely used for output module 8-15:
* Module 8: Byte0..31
* Module 9: Byte32..63
* ...
Page Byte
3 x
This page is entirely used for output module 16-23:
* Module 16: Byte0..31
* Module 17: Byte32..63
* ...

...

Page Byte
10 x
This page is entirely used for output module 72-79:
* Module 72: Byte0..31
* Module 73: Byte32..63
* ...

Following Module structure is used:

Page Byte
1-10 x
Byte 0 (or 32 or 64 ...): Output state of this output (8 outputs, 1 bit per output, 0=OFF, 1=ON)
Byte 1 (or 33 or 65 ...): Dimmer value of output 0 of the concerning module
Byte 2 (or 34 or 66 ...): Dimmer value of output 1 of the concerning module
Byte 3 (or 35 or 67 ...): Dimmer value of output 2 of the concerning module
Byte 4 (or 36 or 68 ...): Dimmer value of output 3 of the concerning module
Byte 5 (or 37 or 69 ...): Dimmer value of output 4 of the concerning module
Byte 6 (or 38 or 70 ...): Dimmer value of output 5 of the concerning module
Byte 7 (or 39 or 71 ...): Dimmer value of output 6 of the concerning module
Byte 8 (or 40 or 72 ...): Dimmer value of output 7 of the concerning module