Energy Module Calibration

From OpenMotics
Revision as of 20:09, 3 May 2015 by Niko (talk | contribs) (Created page with " List of commands for the energy module : Energy Module Commands == Calibration of the voltage == * command '''SVO''' : FUNC_SetVoltage * parameter = 1x4 bytes type f...")
(diff) ← Older revision | Latest revision (diff) | Newer revision → (diff)
Jump to navigation Jump to search


List of commands for the energy module : Energy Module Commands

Calibration of the voltage

  • command SVO : FUNC_SetVoltage
  • parameter = 1x4 bytes type float in [V]
  • There are 3 voltage channels that can be calibrated.
  • The parameter should be the voltage connected to one or more of the voltage channels.
  • Only the channels that have a voltage above 10V (before calibration) will be calibrated. This way you can calibrate every channel separately or in one shot.
  • If the calibrated value deviate more than factor 2 (in both directions), the value will also be 'floored'.

Calibration of the voltage

  • command SCU : FUNC_SetCurrent
  • parameter = 1x4 bytes type float in [A]
  • There are 12 current channels that can be calibrated.
  • The parameter should be the current connected to one or more of the current channels. <<-- what with different current-sensors? should be calibrated with 1 current sensor and an extra parameter should be used to have an extra factor to use in the calculation.
  • Only the channels that have a current above 0.1A (before calibration) will be calibrated. This way you can calibrate every channel separately or in one shot.
  • If the calibrated value deviate more than factor 2 (in both directions), the value will also be 'floored'.