Difference between revisions of "Energy Module Calibration"

From OpenMotics
Jump to navigation Jump to search
m (Pieter moved page EnergyModuleCalibration to Energy Module Calibration: rename)
 
(No difference)

Latest revision as of 09:34, 26 March 2019


List of commands for the energy module : Energy Module Commands

Calibration of the voltage

  • command SVO : FUNC_SetVoltage
  • parameter = 1x4 bytes type float in [V]
  • There are 3 voltage channels that can be calibrated.
  • The parameter should be the voltage connected to one or more of the voltage channels.
  • Only the channels that have a voltage above 10V (before calibration) will be calibrated. This way you can calibrate every channel separately or in one shot.
  • If the calibrated value deviate more than factor 2 (in both directions), the value will also be 'floored'.

Calibration of the current

  • command SCU : FUNC_SetCurrent
  • parameter = 1x4 bytes type float in [A]
  • There are 12 current channels that can be calibrated.
  • The parameter should be the current connected to one or more of the current channels. <<-- what with different current-sensors? should be calibrated with 1 current sensor and an extra parameter should be used to have an extra factor to use in the calculation.
  • Only the channels that have a current above 0.1A (before calibration) will be calibrated. This way you can calibrate every channel separately or in one shot.
  • If the calibrated value deviate more than factor 2 (in both directions), the value will also be 'floored'.