Technical Specifications
- 1 Processor Microchip PIC32MX575F256H
- 1 RS485 bus connection (A and B line) – 1200 meters maximum bus length
- 1 Jumper for RS485 bus termination
- Program Connector
- 8 Digital inputs
- 8 Green input state LEDs
- 1 Orange status LED
- 1 Green power LED
- 2 Network registering buttons
- Automatic network address generation
- 12VDC power supply, reverse polarity protected
- 25mA current consumption
- DIN rail mountable, takes up 3T
- Dimensions: 5.8cm × 5.3cm × 9cm
- Used in conjunction with a Master module
- The Input and Temperature modules feature have identical hardware but runs a different firmware
- Programming language firmware: Pic Basic Pro
- Bootloader: Yes
Firmware
Current version
N/A |
---|
N/A |
Help
Measurement Specifications
- Voltage Measurement
- True RMS
- Accuracy <1%
- Resolution in float (32 bits)
- Frequency Measurement
- Accuracy <1%
- Resolution in float (32 bits)
- Current Measurement
- True RMS
- Accuracy 0.1% (dynamic range 1000:1)
- Depends on accuracy of current clamp connected
- Resolution in float (32 bits)
- Power Measurement
- Accuracy 0.1% (dynamic range 4000:1)
- Depends on accuracy of current clamp connected
- Resolution in float (32 bits)
- Accuracy 0.1% (dynamic range 4000:1)
- Energy Measurement
- per current channel
- resolution integer (32 bits) for Wh
- can be reset
- Voltage Samples per channel (1 period)
- Updated 1Hz
- sampled at 4096Hz (80 samples for 50Hz)
- Resolution in float (32 bits)
- Current Samples per channel(1 period)
- Updated 1Hz
- sampled at 4096Hz (ex. 80 samples for 50Hz)
- Resolution in float (32 bits)
- Voltage frequency samples
- Updated 1Hz
- DC - 20th harmonic
- Resolution in float (32 bits)
- Current frequency samples per channel
- Updated 1Hz
- DC - 20th harmonic
- reference on matching voltage rising zero cross
- Resolution in float (32 bits)
- Current Factor can be set for different current clamps
- ex. current clamp of 5A or 5000A can be connected.
- if a very big current clamp is used, the energy measurement can overflow faster.
Hardware
This module consists of the following PCBs (Printed Circuit Boards):
- OMHEY
- The main PCB that houses all module specific components
- OMHT6
- Generic top panel PCB with all front panel interface components