Difference between revisions of "Energy Module"
Jump to navigation
Jump to search
Line 29: | Line 29: | ||
** True RMS | ** True RMS | ||
** Accuracy 0.1% (dynamic range 1000:1) | ** Accuracy 0.1% (dynamic range 1000:1) | ||
+ | *** Depends on accuracy of current clamp connected | ||
** Resolution in float (32 bits) | ** Resolution in float (32 bits) | ||
* Power Measurement | * Power Measurement | ||
** Accuracy 0.1% (dynamic range 4000:1) | ** Accuracy 0.1% (dynamic range 4000:1) | ||
+ | *** Depends on accuracy of current clamp connected | ||
** Resolution in float (32 bits) | ** Resolution in float (32 bits) | ||
* Energy Measurement | * Energy Measurement |
Revision as of 12:32, 24 December 2016
Technical Specifications
- 12 - 24VDC power supply, reverse polarity protected
- low current consumption
- DIN rail mountable, takes up 6T
- communication via RS485 bus connection (A and B line)
- a Program Connector
- 3 Voltage connections
- Can be configured in WYE and DELTA or single phase
- 50 - 250Vac
- 40 - 75 Hz
- 12 current measurement connections
- grouped per 4 and linked to a voltage connection
- 1 button to address the module
- 3 leds to indicate voltage present.
- 1 status led to indicate the communication
- Bootloader inside
Specifications
- Voltage Measurement
- Trye RMS
- Accuracy <1%
- Resolution in float (32 bits)
- Frequency Measurement
- Accuracy <1%
- Resolution in float (32 bits)
- Current Measurement
- True RMS
- Accuracy 0.1% (dynamic range 1000:1)
- Depends on accuracy of current clamp connected
- Resolution in float (32 bits)
- Power Measurement
- Accuracy 0.1% (dynamic range 4000:1)
- Depends on accuracy of current clamp connected
- Resolution in float (32 bits)
- Accuracy 0.1% (dynamic range 4000:1)
- Energy Measurement
- per current channel
- resolution UINT32 in Wh
- can be reset
- Voltage Samples per channel(1 period)
- Updated 1Hz
- sampled at 4096Hz (ex. 80 samples for 50Hz)
- Resolution in float (32 bits)
- Current Samples per channel(1 period)
- Updated 1Hz
- sampled at 4096Hz (ex. 80 samples for 50Hz)
- Resolution in float (32 bits)
- Voltage frequency samples
- Updated 1Hz
- DC - 20th harmonic
- Resolution in float (32 bits)
- Current frequency samples per channel
- Updated 1Hz
- DC - 20th harmonic
- reference on matching voltage rising zero cross
- Resolution in float (32 bits)
- Current Factor can be set for different current clamps
- ex. current clamp of 5A or 5000A can be connected.
- if a very big current clamp is used, the energy measurement can overflow faster.